sql

Partech TurbiTechw² LA Suspended Solids Sensor Murah

Rp. CALL
Last Updated
16 Mar 2023
Country Origin
United Kingdom
Minimum Order
1 Unit
Category
PARTECH

Specification of Partech TurbiTechw² LA Suspended Solids Sensor Murah

Partech TurbiTechw² LA Suspended Solids Sensor



The TurbiTechw2 LA Sensor has been designed for use in aeration systems typically monitoring Mixed Liquor Suspended Solids also known as Activated Sludge where solids are typically in the range of 2,000 to 5,000 mg/l. The sensor can also measure Returned Activated Sludge (R.A.S.), Surplus Activated Sludge (S.A.S.) and Suspended Solids or Turbidity in any higher range application.



The large optical surface and sample volume combine to ensure that the sensor is providing information that is reliable and representative of the solids present in the process. Deposits of fats and grease on the sensing area do not prevent the sensor from measuring, unlike sensors with small optical surfaces. In addition the sensor incorporates a self cleaning mechanism that ensures that the optical surfaces are kept clean at all times, the cleaning system is designed to avoid problems with ragging and does not smear the optical system. The cleaning system ensures that manual intervention on a routine basis is not required, the sensor should simply be checked as part of general site housekeeping.



The TurbiTechw2 LA Sensor uses infrared light at 860nm and operates using the Light Attenuation Principle. The cleaning mechanism is then sealed by 2 Nitrile ‘H’ Rings that finish the cleaning process. The Nitrile seals can be exchanged for Viton if the process media dictates. The cleaning process is automatically initiated by the 7300w2 Monitor at a user determined frequency. The cleaning process takes only 90 seconds, which means that the sensor is available for 99.5% of the time with a 6 hourly cleaning cycle.



APPLICATIONS




  • Mixed Liquor

  • Aeration Basin

  • Oxidation Ditch

  • Returned Activated Sludge

  • Surplus Activated Sludge



MEASUREMENT PRINCIPAL




  • Light Attenuation

  • Wavelength 860nm



FEATURES




  • Fully automatic Self Cleaning

  • Flexible Mounting System

  • Large Optical Surface



BENEFITS




  • Automated Aeration Control

  • Low Cost of Ownership



COMPATIBLE MONITOR




  • 7300w² Monitor



ALTERNATIVE SENSORS




  • TurbiTechw² HR

  • SoliTechw² IL



SPECIFICATION DATA
















































































Physical



Dimensions (hxwxd)



Ø80mm, 470 mm long



Weight



2.2 kg



Protection Class



IP68



Enclosure Material



Black Acetal Co-Polymer, 316 Stainless Steel, Glass



Seal Material



Polyurethane, Nitrile, with option of Viton



Cable Entry



Integral Cable Gland



Cable Length



10 metres standard, 100 metres maximum



Interface to Monitor


 

Power Supply



12 VDC from Monitor



Sensor Output



ModTechw², RS485



Environmental Data


 

Operating/Storage Temperature



0 to 50ºC



Location



Indoor/Outdoor



Pressure Rating



1Bar or 14.5 psi



Maintenance


 

Service



Seal Service every 3500 cleans (application dependent)



Calibration



The sensor is inherently stable, calibration should be carried out to suit the application. Our recommendation is every 6 months.





Product Publication No. PPPAP/IT00008-18

Publication Date. 07 March 2018

Marketing Division

CV. Putra Andalas Prima

Tel. (+62)-61 8836 9476

Fax. (+62)-61 8836 9476

Email. marketing@putraandalasprima.co.id

Lihat Selengkapnya

Untuk keterangan lebih lanjut, silahkan download PDF ini :

Ulasan

/5
Ulasan
5
4
3
2
1

Foto dari Pembeli

Ulasan dari Pembeli

Filter
Semua
Dengan Foto
5
4
3
2
1
Request a Quote
Produk Siap di Pesan
Rp 0
1